The Richmond City Hall Annex is a 14,489 sq ft municipal facility whose modified bitumen roof, installed in 2000, was approaching the end of its 20-year design life. The City retained Pinpoint to determine exactly how much of the roof was compromised before committing to a repair or replacement budget.
Pinpoint's team scanned all five roof sections (R-1 through R-5) using an RWS roof scanner and Tramex Dec Scanner, cross-checked with DJI Mavic 3 Enterprise thermal drone imaging. A calibration core cut confirmed baseline readings before the full survey began; elevated readings were hand-verified and confirmed with targeted core cuts.
The field membrane itself was graded Failed, with severe granule loss, blisters, ponding, and aged flashing typical of a 25-year-old system near the end of its life. Moisture scanning found the damage was not uniform: R-1 and R-3 held roughly 1,041 sq ft of wet coverboard between them, while R-2, R-4, and R-5 all scanned fully dry. In every wet zone, the coverboard held the moisture and the underlying polyiso insulation tested dry.
A full roof replacement was not necessary. With moisture isolated to the coverboard layer in R-1 and R-3 and insulation intact and dry throughout, Pinpoint recommended a targeted restoration: remove and replace membrane and wet coverboard in the affected sections, skim the remaining dry sections down to the insulation, and install new coverboard and membrane across all five areas.